Filling the water heater, Venting – Kenmore Power Miser 9 Gas Water Heater 153.33096 User Manual
Page 15
15
The temperature-pressure relief valve must be manually operated
at least once a year. Caution should be taken to ensure that
(1) no one is in front of or around the outlet of the temperature-
pressure relief valve discharge line, and (2) the water manually
discharged will not cause any bodily injury or property damage
because the water may be extremely hot.
If after manually operating the valve, it fails to completely reset
and continues to release water, immediately close the cold water
inlet to the water heater, follow the draining instructions, and
replace the temperature-pressure relief valve with a new one.
Filling the Water Heater
Never use this water heater unless it is completely full of water.
To prevent damage to the tank, the tank must be fi lled with water.
Water must fl ow from the hot water faucet before turning “ON”
gas to the water heater.
To fi ll the water heater with water:
• Close the water heater drain valve by inserting a fl at head
screwdriver in the slot on the stem and turn to the right
(clockwise). The drain valve is on the lower front of the water
heater.
• Open the cold water supply valve to the water heater.
NOTE: The cold water supply valve must be left open
when the water heater is in use.
• To insure complete fi lling of the tank, allow air to exit by
opening the nearest hot water faucet. Allow water to run until
a constant fl ow is obtained. This will let air out of the water
heater and the piping.
• Check all water piping and connections for leaks. Repair as
needed.
Venting
VENT DAMPERS - Any vent damper, whether it is operated
thermally or otherwise must be removed if its use inhibits proper
drafting of the water heater.
Thermally Operated Vent Dampers: Gas-fi red water heaters
having thermal effi ciency in excess of 80% may produce a
relatively low fl ue gas temperature. Such temperatures may
not be high enough to properly open thermally operated vent
dampers. This would cause spillage of the fl ue gases and may
cause carbon monoxide poisoning.
Vent dampers must bear evidence of certifi cation as complying
with the current edition of the American National Standard
ANSI Z21.68 (ANSI Z21.66 & 67, respectively, cover electrically
and mechanically actuated vent dampers). Before installation
of any vent damper, consult your local Sears Service Center or
the local gas supplier for further information.
To insure proper venting of this gas-fi red water heater, the correct
vent pipe diameter must be utilized. Any additions or deletions
of other gas appliances on a common vent with this water
heater may adversely affect the operation of the water heater.
Consult your gas supplier if any such changes are planned.
For replacement heater installations where pre-existing venting
is used, the venting must be inspected for obstructions and if
deterioration is present, it must be replaced.
For proper venting in certain installations, a larger diameter vent
pipe may be necessary. Consult your local Sears Service Center
or gas supplier to aid you in determining the proper venting for
your water heater from the vent tables in the current edition of
the National Fuel Gas Code ANSI Z223.1/NFPA 54.
Periodically check the venting system for signs of obstruction or
deterioration and replace if needed.
The combustion and ventilation air flow must not be
obstructed.
The water heater with draft hood installed must be connected
to a chimney or listed vent pipe system, which terminates to the
outdoors. Never operate the water heater unless it is vented
to the outdoors and has adequate air supply to avoid risks of
improper operation, explosion or asphyxiation.
• For proper draft hood attachment, the draft hood legs may
be angled slightly inward.
• Place the draft hood legs in the receiving holes on the top
of the water heater. The legs will snap in the holes to give a
tight fi t. Secure the legs to top with sheet metal screws. See
Figure 17.
• Place the vent pipe over the draft hood. With the vent pipe
in position, drill a small hole through both the vent pipe and
draft hood. Secure them together with a sheet metal screw.
Obstructed or deteriorated vent systems may present serious
health risk or asphyxiation.