TROUBLESHOOTING GUIDE

Start Up Conditions

Thermal Expansion

Water supply system may, because of such events as high line
pressure, frequent cut-offs and the effects of water hammer have
installed devices such as pressure reducing valves, check valves,
back fl ow preventers, etc., to control these types of problems.
When these devices are not equipped with an internal by-pass,
and no other measures are taken, the devices cause the water
system to be closed. As water is heated, it expands (thermal
expansion) and closed systems do not allow for the expansion
of heated water.

The water within the water heater tank expands as it is heated and
increases the pressure of the water system. If the relieving point
of water heater’s temperature-pressure relief valve is reached,
the valve will relieve the excess pressure. The temperature-
pressure relief valve is not intended for the constant relief
of thermal expansion.
This is an unacceptable condition and
must be corrected.

It is recommended that any devices installed which could
create a closed system have a by-pass and/or the system have
an expansion tank or device to relieve the pressure built by
thermal expansion. Thermal expansion tanks are available from
Sears stores and through the Sears Service Centers. Contact
the local plumbing inspector, water supplier and/or the Sears
Service Center for assistance in controlling these situations,
see Figure 34.

Thermal Expansion Tank Specifi cations

Model

Number

Tank

Capacity

In Gallons

Dimensions

in Inches

Pipe

Fitting

On Tank

Diameter

Length

153.331020

2

8 (203 mm) 12-3/4 (323 mm) 3/4” Male

153.331050

5

11 (279 mm) 14-3/4 (375 mm)

3/4” Male

Expansion Tank Sizing Chart

Expansion

Tank

Capacity

Needed

Inlet*

Water

Pressure

Water Heater Capacity (Gallons)

30

40

50

66

82

40 psi

2

2

2

5

5

50 psi

2

2

2

5

5

60 psi

2

2

2

5

5

70 psi

2

2

5

5

5

80 psi

2

5

5

5

5

*Highest recorded inlet water pressure in a 24 hour period or
regulated water pressure.

NOTE: Expansion tanks are pre-charged with a 40 psi air
charge. If the inlet water pressure is higher than 40 psi, the
expansion tank’s air pressure must be adjusted to match
that pressure, but must not be higher than 80 psi.

FIGURE 34.

Strange Sounds

Possible noises due to expansion and contraction of some metal
parts during periods of heat-up and cool-down do not represent
harmful or dangerous conditions.

Condensation causes sizzling and popping within the burner area
during heating and cooling periods and should be considered
normal. See Condensation section.

Draft Hood Operation

Check draft hood operation by performing a worst case
depressurization of the building. With all doors and windows
closed, and with all air handling equipment and exhaust fans
operating such as furnaces, clothes dryers, range hoods and
bathroom fans, a match fl ame should still be drawn into the
draft hood of the water heater with its burner fi ring. If the fl ame
is not drawn toward the draft hood after 15 minutes of burner
operation, shut off water heater and make necessary air supply
changes to correct.