Restore factory, Caution – KMC FLEXSTATTM BAC-10000 User Manual
Page 15

BAC-10000 Series
15
Operation Guide, Rev. J
Restore Factory
Restore Factory (restoring the FlexStat to the factory
settings) does the following:
• Clears present values.
• Restores the object database/configuration to the
defaults.
• Restarts the controller’s (factory installed) Con-
trol Basic programs.
NOTE: The MAC address and device instance are
not restored to their original defaults, and
custom Control Basic programs are not
deleted. If custom Control Basic programs are
installed, all factory programs are restarted
but all custom Control Basic programs are
halted. Custom programs may be restarted by
loading/running the programs from the CB
CAUTION
When returned to factory defaults, analog out-
puts will go to zero and relays will go to their
normally open state. Before restarting the ther-
mostat, manually override equipment as needed.
ADVANCED
APPLICATION
CB PROGRAMS
COMMUNICATION
DATE/TIME
DEVICE
LIMITS
SECURITY
DEVICE
INSTANCE: 1
NAME: FlexStat_101
LOCATION: KMC Controls
RESTART: NO
RESTORE FACTORY:
YES
RESTART REQUIRED!
CANCEL
RESTART
CAUTION
After a return to factory defaults, applications are
unconfigured. You must select the desired appli-
cation and appropriate settings before connected
equipment will operate properly. (See
.)
To restore the FlexStat to factory settings:
1. Select Restore Factory from the Advanced > De-
vice menu.
2. When prompted for the required restart, press
Enter. (To Cancel, press the right button and then
Enter or just let the display time-out).
3. After the FlexStat has restarted, review the set-
tings and reconfigure as needed.