beautypg.com

4 connecting the equipotential bonding circuit – Siemens Industrial PC Simatic Panel PC 677B User Manual

Page 23

background image

Connecting

4.4 Connecting the Equipotential Bonding Circuit

SIMATIC Panel PC 677B
Operating Instructions (Compact), 06/2008, A5E02217246-01

23

4.4

Connecting the Equipotential Bonding Circuit

A low-resistance ground connection ensures that interference signals generated by external

power supply cables, signal cables or cables to the I/O modules are safely discharged to

ground.
The equipotential bonding connection of the device is located underneath the device and is

identified by the following symbol:

Figure 4-1

Equipotential Bonding

Connecting the Equipotential Bonding Circuit

You require a TORX T20 screwdriver to connect the equipotential bonding conductor.

Steps for connecting the equipotential bonding
(1) Connect the equipotential bonding connection (M4 thread) (1)

on the device (large surface, large-area contact) with the

central grounding point of the control cabinet.

The minimum permissible cross-section is 5 mm

2

.