14.2 Ventilation requirements

The room containing the appliance should have an air supply in accordance with B.S. 5440 part 2 1989.
1 All rooms require an opening window or equivalent, and some rooms will require a permanent vent as

well.

2 For room volumes up to 5 m

3

an air vent of 100 cm

2

is required.

3 If the room has a door that opens directly to the outside, and the room exceeds 1 m

3

no air vent is

required.

4 For room volumes between 5 m

3

and 10 m

3

an air vent of 50 cm

2

is required.

5 If there are other fuel burning appliances in the same room B.S. 5440 part 2 1989 should be

consulted to determine the air vent requirements.

6 This appliance must not be installed in a bed sitting room of less than 20 m

3

or in a bathroom or

shower room.

Windows and permanent vents should therefore not be blocked or removed without first consulting a
Corgi gas installer. Failure to install appliances correctly is dangerous and could lead to
prosecution.

14.3

Connecting to natural and LPG gas (Please see connection diagram)

Make the connection to the appliance using flexible bayonet style hose in accordance to
B.S. 669. The hose connection at the rear of the appliance has a ½” BSP internal thread.
Please use seal C between the flexible connection L and the appliance supply tube B.
When making the connection, make sure that no stress of any kind is applied to the
cooker and that the hose does not touch any sharp edges. If connecting to LPG the
bayonet hose must have red bands on it.