Extending the Anti-tip Foot
1.4.4
Installing the Server Into the Slide-Rail
Assemblies
Use this procedure to install the server chassis, with mounting brackets, into the
slide-rail assemblies that are mounted to the rack.
Caution –
This procedure requires a minimum of two people because of the weight
of the server. Attempting this procedure alone could result in equipment damage or
personal injury.
1. Push the slide-rails into the slide-rail assemblies as far as possible.
2. Raise the server so that the rear ends of the mounting brackets are aligned with
the slide-rail assemblies that are mounted in the equipment rack. See
3. Insert the mounting brackets into the slide-rails, and then push the server into the
rack until the mounting brackets encounter the slide-rail stops (approximately 12
inches, or 30 cm).