11-5. In Case of Compressor Malfunction

CAUTION

Should the compressor malfunction, be sure to make the switch to a replacement

compressor as quickly as possible.
Use only the tools indicated exclusively for R410A. See "11-3. Tools

Specifically for R410A."

11-5-1. Procedure for Replacing Compressor

(1) Recovering refrigerant

Any remaining refrigerant inside the unit should not be

released to the atmosphere, but recovered using the

refrigerant recovery unit for R410A.
Do not reuse the recovered refrigerant, since it will contain

impurities.

(2) Replacing Compressor

Soon after removing seals of both discharge and suction

tubes of the new compressor, replace it quickly.

(3) Checking for sealing

Use nitrogen gas for the pressurized gas, and never use a

refrigerant other than R410A. Also do not use oxygen or

any flammable gas.

(4) Evacuation

Use a solenoid valve-installed vacuum pump so that

even if power is cut off in the middle of evacuation of air

due to a power interruption, the valve will prevent the

pump oil from flowing back.
The equipment may be damaged if moisture remains in

the tubing, thus carry out the evacuation thoroughly.
When using a vacuum pump with exhaust air volume more

than 0.883 cu.ft./min. and ultimate vacuum pressure rate

of 50 micron Hg.

Standard time for evacuation

(1) Recover refrigerant

OK

(2) Replace compressor

OK

(3) Check for sealing

OK

(4) Evacuation

OK

(5) Recharge

Length of tubing

Evacuation time

Less than 33 ft. (10 m)

More than 10 minutes

More than 33 ft. (10 m)

More than 15 minutes

61