13

(A)+(B)

(A) Power Supply Wiring Length (ft)

(C) Control

Fuse or Circuit

AWG

(B) Power Line Length (ft)

Line Length (ft)

Model

(#14)

(#12)

(#14)

Breaker Capacity

C1872, CL1872

131 (Max.)

230 (Max.)

98 (Max.)

20A

C2472, CL2472

131 (Max.)

230 (Max.)

131 (Max.)

20A

3-7. Recommended Wire Length and Diameter

Regulations on wiring diameter differ from locality to locality. For field wiring

requirements, please refer to your local electrical codes. Carefully observe these

regulations when carrying out the installation.

Table 5 lists recommended wire lengths and diameters for power supply systems.

Refer to the wiring system diagram (Fig. 23) for the meaning of (A), (B), and (C) in

Table 5.

Refer to your local codes or in the absence of local codes see the National Elec-

tric Code: ANSI/NFPA70.

NOTE

Fig. 23

WIRING SYSTEM DIAGRAM

Be sure to comply with local codes on running the wire

from the indoor unit to the outdoor unit (size of wire and

wiring method, etc.).

Each wire must be firmly connected.

No wire should be allowed to touch refrigerant tubing, the

compressor, or any moving part.

Disconnect
switch

1

2

3

1

2

3

4

5

6

Grounding line

230/208V

230/208V

230/208V

INDOOR

UNIT

OUTDOOR

UNIT

Field supply

Grounding
line

L

1

L

2

Po

w

e

r

su

pply

S

ing

le pha

s

e 2

3

0/20

8

V 60HZ

Terminal

Terminal

(A)

(B)

(C)

(B)

CAUTION

Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram.

The indoor unit draws its power from the outdoor unit.

Do not run wiring for antenna, signal, or power lines of television, radio, stereo, telephone,

security system, or intercom any closer than 3'4" (1 m) from the power cable and wires

between the indoor and outdoor units. Electrical noise may affect the operation.

To avoid the risk of electric shock, each air conditioner

unit must be grounded.

For the installation of a grounding device, please

observe local electrical codes.

Grounding is necessary, especially for units using

inverter circuits, in order to release charged electricity

and electrical noise caused by high tension.

Otherwise, electrical shock may occur.

Place a dedicated ground more than 7' (2 m) away from

other grounds and do not have it shared with other elec-

tric appliances.

WARNING

# ... AWG (American Wire Gauge)

Table 5

WARNING

*

*

Disconnect switch may be required by national

or local codes.

NOTE

Always comply with national and local code

requirements.

CAUTION

07-154 CL1872-2472 6/12/07 3:19 PM Page 13