Refrigerant flow diagram, 1. refrigerant flow diagram, Insulation of refrigerant tubing – Sanyo CL2472 User Manual

Page 24

background image

Compressor

Accumulator

Wide tube

service

valve

Wide tube

Narrow

tube

service

valve

Narrow tube

Heat exchanger

Heat exchanger

Muffler

Cooling cycle

Indoor unit

Outdoor unit

Electric

expansion

valve

M

*1

*1 O.D.1/2"(12.7mm) ... 1872 class

O.D.5/8"(15.88mm) ... 2472 class

O.D.

1/4"

(6.35 mm)

H.P.

High pressure

switch

4. REFRIGERANT FLOW DIAGRAM

4-1. Refrigerant Flow Diagram

Indoor Unit

KS1872

KS2472

Outdoor Unit C1872 C2472

CL1872 CL2472

Insulation of Refrigerant Tubing

Because capillary tubing is used in the outdoor unit, both the

wide and narrow tubes of this air conditioner become cold. To

prevent heat loss and wet floors due to dripping of

condensation, both tubes must be well insulated with a

proper insulation material. The thickness of the insulation

should be a min. 5/16"(8 mm).

After a tube has been insulated,

never try to bend it into a narrow

curve because it can cause the tube

to break or crack.

Wide tube

Thickness:

Min. 5/16"(8 mm)

Insulation

Narrow tube

Thickness:

Min. 5/16"(8 mm)

IMPORTANT

CAUTION

24