Compressor discharge temperature control

Freeze prevention

During COOL or DRY operation, freezing is detected and

operation is stopped when the temperature of the indoor heat

exchanger matches the conditions below.

1. Freeze-prevention operation is engaged when the

temperature of the indoor heat exchanger is below 43°F(6°C).

2. Restart after freeze-prevention operation occurs when the

temperature of the indoor heat exchanger reaches 46°F(8°C)

or above.

a.

Area: Automatic capacity control

b.

When the temperature drops below Point A, the operation

frequency is reduced by a certain proportion.

c.

Area: Frequency increase is prohibited.

d.

When the temperature reaches Point C or above, freezing

prevention is ended and control is the same as in the

a

area.

*

When the temperature drops to below 36°F(2°C)

(continuously for 2 minutes or longer), the compressor stops.

Once the freeze condition is detected, the air conditioner will

work less than the maximum frequency until it is turned off.

The Freeze Prevention Control during the Low Ambient Cooling

Mode (outside air temperature:59°F(15°C) or lower) is as follows.

The compressor stops when the temperature of indoor heat

exchanger becomes less than 36°F(2°C).

The compressor restarts when the temperature of indoor heat

exchanger becomes 46°F(8°C) or higher.

A

*

B

C

a

b

c

d

Indoor heat exchanger

temperature

°F

(

°C

)

36

(2)

43

(6)

46

(8)

This function controls the operation frequency to prevent the

compressor discharge temperature from rising more than a

specified temperature.

a.

Area: Automatic capacity control.

b.

When the temperature rises above Point A, the operation

frequency is reduced at a specified rate.

c.

Area: Further frequency increase is prohibited.

d.

When the temperature falls below Point B, prevention of a rise

in frequency is released and the air conditioner operates as in

a

area.

*

The compressor will stop if the temperature of the compressor

discharge exceeds 248°F(120°C) due to shortage of gas or

other reason.

Approx.

214

(101)

A

B

a

b

c

d

Compressor discharge temperature

°F

(

°C

)

Approx.

201

(94)

NOTE

8-2. Protective Functions

This function prevents the circuit breaker or fuse from operating

to open the circuit. This function works when electrical current

has increased due to an increase in the cooling load,

or to a decrease in the power supply voltage. In these cases,

operation frequency is reduced or operation is interrupted auto-

matically to control the electrical current for operation.

When the cause of the increase in electrical current is rectified,

the system will resume operation in the original mode.

Cooling Dry

Peak current cut-off trips

22.5

Hz down

14.0

(A)

CT (Peak current cut-off control)

(CLxx models only)

45

This manual is related to the following products: