PC/TS Adapter
Quick Reference Guide
8
PC/TS Adapter
A5E00078070-02
As the adapter receives its power supply via the MPI/DP in-
terface, only those interfaces can be used which provide
24 V DC and 5 V DC with the voltages and currents specified
in the table in the ”Technical Specifications” (Chapter 7). The-
refore a connection at the free end of a PROFIBUS cable is
not possible.
7
4
9
8
3
9-pin subminiature D:
1
2
3
4
5
6
7
8
9
GND
DCD
RXD
TXD
DTR
DSR
RTS
CTS
RI
P24V
M24V
P5V
M5V
RTSAS
RTS_PG
LTG_A
LTG_B
9-pin subminiature D:
CMOS
RS232
Adapter
+5V
50mA (typ)
40mA (typ)
PC potential area S7/M7/C7 potential area
RS232 Interface
19.2/38.4 kbps
Electronics
S1
ACTIVE POWER
2
6
MPI/DP Interface
9.6 to 1500 Kbps
5
Figure 1-7
Block Diagram of the Adapter
The adapter provides electrical isolation between its MPI/DP
interface and RS232 interface within a safety extra-low
voltage (SELV) circuit, thus allowing direct operation even on
ungrounded S7/M7/C7 systems.
RS232 side:
S
See Figures 1-1/1-2 “PC/TS Adapter in the System” for
direct connection details. An RS232 cable is required to
connect a PC/programming device to the adapter’s
RS232 interface (COM2-PC-compatible). This cable must