Determine the alarm organization, Organization of system operation, 3 determine the alarm organization – Siemens FC700A User Manual
Page 57: 4 organization of system operation
Alarm concept
57
Siemens Building Technologies
007836_a_en_--.doc
Fire & Security Products
03.2004
24.3 Determine the alarm organization
–
The FC700A fire detection system has up to 64 programmable organization lev-
els (AREAS)
–
A number of "Alarm variants" are possible (can be selected per ZONE)
–
The time countdown memories "V1" and "V2" must be specified individually
–
The time countdown memory "V2" can be defined per ZONE (if required)
–
Various special local functions are provided
–
The alarm organization is programmed individually (via maintenance PC)
24.4 Organization of system operation
The place of operation of the fire detection system must be determined from an
organizational point of view
If required a second operating facility must be provided
If operating units are particularly exposed, they must be fitted with a lockable
Plexiglas door (H26T030 + Z3S200)
The type of event and the location are displayed on the operating unit in plain
text
The locations (rooms etc.) are individually defined by means of the "User text"
(via maintenance PC)
If required, an additional event-related instruction, a so-called counter-
measures text, can be allocated
The fire detection system may only be operated by instructed personnel (operat-
ing access is therefore protected by password or key switch)
Details of control terminal FT700A see chapter 12