Auxiliary power supply, Configuration, Block diagram – Siemens FC700A User Manual
Page 26: Modules, 11 auxiliary power supply, 1 configuration, 2 block diagram, 3 modules, Fc700a

Auxiliary power supply
26
Siemens Building Technologies
007836_a_en_--.doc
Fire & Security Products
03.2004
11
Auxiliary power supply
11.1 Configuration
31
51
23
27
37
47
57
46
56
A
28
38
48
58
AX1210
AX1201
or
Mains
terminals
AX1210
AX1201
or
View A
E3C01
1
B2
F
020
Z3
I47
0
H38G310
Module chassis
view 'Modules'
Cabinet front view
absolutely essential
B2F020
Converter 115/230VAC
-> 29.6VDC/6A
E3C011
Battery charging module
AX1201 / AX1210
Batteries
Z3I470
Cable set, terminal strip
with card holder
11.2 Block
diagram
* TF = Temperature sensor for battery temperature monitoring
Mains
Basic emergency
power supply
Extension
B2F020
TF*
TF*
Batteries
AX12..
Batteries
AX12..
Monitoring via HW monitoring path
FC700A
Mains
B2F020
E3C011
E3C011
Battery charging unit
H38G310
Cascading
Details see document 007831, chapter 'Cascading principle'
To activate the supervision path of the E3C011, the device "Fu supply ext. supply
supervision" must be created in the tool SWE700A.
11.3 Modules
Component Order-No. Description
Notes
H38G310
484930
Housing set
Door without cut-out
B2F020
470588
Converter 115/230VAC -> 29,6VDC 6A
E3C011 505479 Battery
charging
unit
Z3I470
484341
Cable set with card holder
AX1201
225487
Battery 12V / 27Ah
Capacity based battery make 'ALARMCOM' (FIAMM)
AX1210
475570
Battery 12V / 15Ah