Line modules

37

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004


15.4 Detection line "collective" SynoLINE600/-Ex

All detectors on a line have the same collective address (ZONE)

Number of detectors per line max. 25 with KMK1

Line termination depending on application by means of Transzorb or EOL22 (Ex)

Connectable types of detectors and connection see document 007831

1

8 Stub lines

SB3

24VDC

E3M080

8

HI62xC

OP620C

Line termination: Transzorb 20V/EOL22

Line resistance: max.150Ω

DC1192

DO1101A-Ex

DT1101xA-Ex

DF1101-Ex

Line termination

EOL22 (Ex)

DLR11 . .

DLO1191

DF1191/92

DM1103

DBZ1197A

OP620C

HI62xC

DM1103

SynoLINE600-Ex

SynoLINE600

2

3

Some detectors have different loading factors, to evaluate how many special de-
tectors can be connected to one collective line see chapter 16.2.