Page 37: Number of detectors per line max. 25 with kmk1
Line modules
37
Siemens Building Technologies
007836_a_en_--.doc
Fire & Security Products
03.2004
15.4 Detection line "collective" SynoLINE600/-Ex
All detectors on a line have the same collective address (ZONE)
Number of detectors per line max. 25 with KMK1
Line termination depending on application by means of Transzorb or EOL22 (Ex)
Connectable types of detectors and connection see document 007831
1
8 Stub lines
SB3
24VDC
E3M080
8
HI62xC
OP620C
Line termination: Transzorb 20V/EOL22
Line resistance: max.150Ω
DC1192
DO1101A-Ex
DT1101xA-Ex
DF1101-Ex
Line termination
EOL22 (Ex)
DLR11 . .
DLO1191
DF1191/92
DM1103
DBZ1197A
OP620C
HI62xC
DM1103
SynoLINE600-Ex
SynoLINE600
2
3
Some detectors have different loading factors, to evaluate how many special de-
tectors can be connected to one collective line see chapter 16.2.