Power supply (24v), 6 power supply (24v), Control unit fc700a – Siemens FC700A User Manual
Page 30
Control terminal B3Q700 (FC/FT)
30
Siemens Building Technologies
007836_a_en_--.doc
Fire & Security Products
03.2004
12.5 Connection lines between control unit and external operating
units
When planning a system the following condition must be complied with:
At least one operating unit must comply with standard EN54, i.e. it must be
equipped with emergency operation and emergency power supply.
EN54 requirements:
Communication as loop line -> design C-Bus as a loop line
Operating units also with emergency operation -> 3 additional wires
Second de-coupled 24V supply -> 3 additional wires or autonomous power
supply
The number of wires in the connection cable depends on the application and the
distances between the stations:
Application C-Bus
24V
supply
Emergency power
supply
Emergency opera-
tion circuit
Number of wires
24V supply from
control unit
EN54 complied with
✔
(2 wires)
✔
(3 wires)
✔
(3 wires)
✔
(3 wires)
11
24V supply from
control unit without
emergency operation
and emergency
power supply
✔
(2 wires)
✔
(3 wires)
5
Note:
–
Emergency operation circuit required including between CPUs or for a sepa-
rately connected Gateway
–
Emergency operation circuit and emergency supply are not designed as a loop
line
–
Emergency supply via separate cable or C-Bus feedback
12.6 Power supply (24V)
Operating unit B3Q700 is designed for the voltage range 18...45VDC
The maximum current at 24V is 400mA
Max. Length of line (approximate):
–
For cables ø 0.8mm -> 180m
–
For cable cross-section 1mm
2
-> 360m
The current consumption for the options (parallel indicator panel, LON-module)
must be taken into account separately
Control unit FC700A
Options
Control terminal FT700A
2…11
leads
Loop C-Bus
max. 1000m per loop with ∅0,6mm G51 (incl. return line)
max. 1400m per loop with ∅0,8mm G51 (incl. return line)
Control terminal
FT700A
B3R051 (Parallel indicator panel)
E3I040 (LON module)
Printer