Power supply
52
Siemens Building Technologies
007836_a_en_--.doc
Fire & Security Products
03.2004
22 Power
supply
22.1 Concept
The power supply for the FC700A fire detection system consists of:
Converter
(mains voltage -> system voltage 29,6V)
Battery charging unit (by means of E3C011)
Batteries (lead)
(capacity as required)
22.2 Special
functions
–
Automatic battery load test
–
Battery charging characteristic can be programmed according to make
22.3 Application
–
Determine required battery capacity individually -> see chapter 23
–
Max. 27Ah per battery charging unit (> 27Ah = auxiliary power supply)
–
Parallel operation of several battery charging units possible
–
Battery lead without EMI-protection (battery cannot be mounted separately)
22.4 Power supply for the control unit
Battery charging module E3C011 required
I-Bus
Mains
E3C011
Batteries
AX12..
B3Q700
29,6V
FC
TF*
B2F020
40...220VA
22.5 Auxiliary
power
supply
* TF = Temperature sensor for battery temperature monitoring
Mains
Basic emergency
power supply
Extension
FT
B2F020
TF*
TF*
C-Bus
Batteries
AX12..
Batteries
AX12..
Monitoring via HW monitoring path
FC
Mains
B2F020
E3C011
E3C011
24V
Battery charging
unit