Logical and physical structure
In the FC700A fire detection system, the logical structure is completely separated
from the physical structure. This enables the greatest possible flexibility. Display
and control terminal are based on the geographical and organizational aspects and
are independent of the actual hardware installation of the detector network.
Geographical features (-> building structure)
Main building (Area)
1st floor
2nd floor
ground floor
1
st
floor (Section)
1st floor
Room 104
Room 103
Room 102
Room 101
Room 104 (Zone)
Logical structure
The logical structure is a configuration of the
geographical features of a system. It can be
modified easily to the building structure, room
utilization etc.
Within the same control unit the logical struc-
ture is independent of the wiring of the detec-
tor network.
Linking
The lowest levels of both structures are linked
to each other. It is determined which physical
devices (e.g. detectors) are in which logical or
geographical location.
Physical structure
The physical structure is a configuration of the
hardware. It results from the hardware instal-
lation. The number of used levels is depend-
ing on the type of hardware.
C-Bus
Control unit ‘FC’
SynoLOOP
I-Bus
Control terminal ‘FT’
Area
Section
Zone
Element
Main
building
Ground
floor
1st
floor
2nd
floor
Room
102
Room
103
Room
104
Canteen
Linking
Level 1
Level 2
Ware
house
Reception
EDP
room
logical structure
Station
Level 1
Level 2
Function unit
Device
physical structure
Line 1
Line 2
Line 3
Line 4
Line modules E3M111