Limitations of C-Bus participants

20

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004


8

Limitations of C-Bus participants

This chapter describes the quantitative limits of the FC700A station.
The selection of the station type depends on the requirements. The following vari-
ants are available:

Station type

Modules

Flash ROM

(2x1024Kx8Bit)

'Program file'

SRAM

Soldered

EPROM set

RAM set

FC700A B3Q700 CIY00760

4x512Kx8Bit –

FT700A B3Q700

CTY00760

4x512Kx8Bit –

FG700A E3H020

CKQ007.60

(2x512Kx8Bit)

2 x Z3S070

(2x512Kx8Bit)

(Assembly ex works)

8.1

Main CPU limits

8.1.1

Maximum number of devices

1000 devices (with AMPK=1) per FC700A.

8.1.2

Limits in the logical structure

The limits in the logical structure are given by the node-type, by the highest possi-
ble CSX number and the maximum amount of display-digits. These limits are given
by the system and are independent of the memory capacity.

Table 'Limits of the logical structure'

Maximum rating

AREAS per STATION

Maximum rating

SECTIONS per AREA

Maximum rating

ZONES per SECTION

Maximum rating

ELEMENTS per ZONE

... 4

…255

…255

…99

International 5: …255

8.1.3

Maximum number of criteria in zones control 4 and 6

The maximum number of control zones with 16 criteria is limited by 200.

To optimize the performance of your system minimize the number of CPU-overlapping controls as
much as possible.
A maximum of 40 CPU-overlapping controls (zone control 6) are admissible per C-Bus.

8.1.4

Maximum number of ZONE time channel

Max. 16 ZONES time channel are permitted per station.