beautypg.com

Quiescent current table, 3 quiescent current table, Emergency power supply – Siemens FC700A User Manual

Page 55: Quiescent current when on battery operation (24v)

background image

Emergency power supply

55

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004


23.3 Quiescent current table

Quiescent current when on battery operation (24V)

As basis for individual calculation of emergency power supply

The current for the 5V supply is included in these values

Module

Quiescent current at 24VDC

(typical)

Additional current with alarm condition

B2F020 0

0

B3Q700

100mA LCD backlight ’inactive’ (active = + 200mA)

+ 230mA

B3Q580 20mA

+

160mA

B3Q590/595 18mA

+

167mA

B3R051

40mA

all LEDs inactive

+ 2mA

per activated LED

E3C011 20mA

0

E3G050

10mA

all relays inactive

+ 11mA per activated relay

E3G060

25mA

all control lines terminated

+ 23mA per activated control line, without external load

E3G070

25mA

control line ’Horn’ terminated

+ 34mA without external load (horns etc.)

E3H020 100mA

0

E3I020 25mA

0

E3L020

22mA

+ ..mA depends from the activated device

E3L030

18mA

+ 40mA without external load (FBF, HM, FSK)

E3M080

85mA

37mA + 6mA per terminated line

+ 10mA per line in alarm

E3M111

210mA (=50mA + 0,31mA per D–Bus device) 1)

(without external 24V load)

0

K3G060

6mA

+ 3mA

per relay

K3R072

40mA

+ 2mA

per activated LED

0

per activated relay

Z3B171

0

+ 27mA per activated relay

E3I040

15mA

without external 24V load

0

K3I050

15mA

+ 0mA

or 4mA per activated LED

K3I110

24mA

max. 184mA all relay activated incl. service LED

+ 10mA per activated relay
+ 0,5mA per input with closed contact

1

Only valid for device with APMK = 1 (multiply value for devices > 1)