Page 45: Out door temp. adap ta ti on, de lay ed 45, Remote operation, Optimization with room sensor, 6 delayed outdoor temperature adaptation, 7 outdoor temperature-dependent advance heating
Note!
Summer mode only becomes effective when the controller is in automatic mode (
).
5.6 Delayed outdoor temperature adaptation
The calculated outdoor temperature is used to determine the flow temperature set point. The
heat response is delayed when the outdoor temperature either decreases, or increases and de-
creases. If the outdoor temperature varies by, for example, 12 °C within a very short period of
time, the calculated outdoor temperature is adapted to the actual outdoor temperature in small
steps. Assuming a
Delay of 3 °C/h, the adaptation would take t
C
C h
=
=
°
°
12
3
/
4 h.
Note!
The delayed outdoor temperature adaptation helps avoid unnecessary overloads of central
heating stations in combination with either overheated buildings occurring, for example, due to
warm winds, or temporarily insufficient heating due to the outdoor sensor being exposed to di-
rect sunshine.
In the operating level, the outdoor temperature blinks on the display while delayed outdoor tem-
perature adaptation is active. The calculated outdoor temperature is displayed.
Function
WE
Configuration
Delayed outdoor temperature
adaptation
OFF
3 °C/h
Co5 -> Fb04 = ON
Ab
When outdoor temperature drops
Auf Ab When outdoor temperature drops or rises
Delay / 0.2 to 6.0 °C/h
5.7 Outdoor temperature-dependent advance heating
The controller activates the heating depending on the outdoor temperature before the
time-of-use starts in normal operation. The
Advance heating time is based on an outdoor tem-
perature of –12 °C. The advance heating time is shorter when the outdoor temperature is
higher.
Functions
WE
Configuration
Optimization
OFF
120 min
Co1, 2, 3 -> Fb05 = ON, Select:
1
Advance heating time / 0 to 360 min
Outdoor sensor AF1, 2, 3
Co1, 2, 3 -> Fb02 = ON
EB 5179 EN
45
Functions of the heating circuit