3 fixed set point con trol 41, Fixed set point control – Samson Trovis 5100 User Manual
Page 41
The
Max. flow temperature and Min. flow temperature parameters mark the upper and lower lim-
its of the flow temperature.
Functions
WE
Configuration
4-point characteristic
OFF
Co1, 2, 3 -> Fb10 = ON
4-point characteristic
OFF
Co4 -> Fb03 = ON (Anl 3, 5, 8 and 10)
Parameters
WE
Parameter level / Range of values
Flow temperature
Point 1
Point 2
Point 3
Point 4
70 °C
55 °C
40 °C
25 °C
PA1, 2, 3 / 20 to 130 °C
Outdoor temperature
Point 1
Point 2
Point 3
Point 4
–15°C
– 5 °C
5 °C
15 °C
PA1, 2, 3 / –30 to 90 °C
Return flow temperature Point 1
Point 2
Point 3
Point 4
65 °C
50 °C
35 °C
20 °C
PA1, 2, 3 / 20 to 90 °C
Set-back difference
Points 2, 3
20 °C PA1, 2, 3 / 0 to 50 °C
Max. flow temperature
90 °C PA1, 2, 3 / 20 to 130 °C
Min. flow temperature
20 °C PA1, 2, 3 / 20 to 130 °C
EB 5179 EN
41
Functions of the heating circuit
t
VLmax
t
VLmin
t
VL
100
90
80
70
60
50
40
30
20
10
[˚C]
20
15
10
5
0
–5
–10 –15 –20
P1
P2
P3
P4
[˚C]
t
A
Fig. 3 · 4-point characteristic
P1 to 4 Points 1 to 4
tVL
Flow temperature
tA
Outdoor temperature
...min
Minimum tVL
...max
Maximum tVL
4-point characteristic
Reduced 4-point
characteristic