Series 90-70 Hot Standby CPU Redundancy User’s Guide – December 1993
GFK-0827
Following are several examples that illustrate the above guidelines. Each example gives
the role of each unit, its current operating mode, and the state of the LEDs on the RCMs.
An X indicates that the corresponding LED and %S bit is ON.
A. Role switches allowed on both units.
Primary Unit
Secondary Unit
Active
Backup
RUN/ENABLED
RUN/ENABLED
X OK
X OK
X LOC_RDY
X LOC_RDY
X LOC_ACT
LOC_ACT
X REM_RDY
X REM_RDY
REM_ACT
X REM_ACT
B. Role switches allowed on both units.
Primary Unit
Secondary Unit
Active
Backup
RUN/DISABLED
RUN/ENABLED
X OK
X OK
LOC_RDY
X LOC_RDY
X LOC_ACT
LOC_ACT
X REM_RDY
REM_RDY
REM_ACT
X REM_ACT
Note that the Secondary unit drives the outputs in this case.
C. Role switches are not allowed on either unit.
Primary Unit
Secondary Unit
Active
Backup
RUN/ENABLED
RUN/DISABLED
X OK
X OK
X LOC_RDY
LOC_RDY
X LOC_ACT
LOC_ACT
REM_RDY
X REM_RDY
REM_ACT
X REM_ACT
D. Role switches are allowed on both units.
Primary Unit
Secondary Unit
Active
Backup
RUN/DISABLED
RUN/DISABLED
X OK
X OK
LOC_RDY
LOC_RDY
X LOC_ACT
LOC_ACT
REM_RDY
REM_RDY
REM_ACT
X REM_ACT