icos -

Installation & Servicing

INSTALLATION

FLUE OUTLET

17 PREPARING THE WALL

IMPORTANT. Ensure that, during the cutting operation,
masonry falling outside of the building does not cause
damage or personal injury.

1. Cut the flue hole (preferably with a 5" core boring

tool), ensuring that the hole is square to the wall.
Both wall faces immediately around the cut hole
should be flat.

2. Drill 3 holes with a 7.5mm / 8mm masonry drill and

insert the plastic plugs provided, for the wall
mounting plate and the jacking screw plate.

Note.

If using the stand-off kit then drill 4 holes (choosing
one from each group but not the jacking screw).

3. Locate 2 No.14 x 50mm screws in the piping frame

(one at each side, in any of the 3 holes provided at
each side) and screw home.

Note.

If using the stand-off kit then locate the stand-off
channel and screw home.

19 SETTING THE FLUE - SIDE

Wall thicknesses of 170 to 395mm

18 SETTING THE FLUE - REAR

Wall thicknesses of 210 to 435mm

Notes.
a.
If using the extension ducts go to Frame 18.
b. For shorter flue requirements use non telescopic B

Pack.

1. Measure and note wall thickness X. Refer to Frame 14.
2. Measure distance from side of boiler to inside of wall

and add to wall thickness X=L. Refer to Frame 14.

3. Add 115mm to dimension L and set telescopic flue

length as indicated in drawing.

4. Using a 3.5mm drill bit, drill two holes in outer air duct

taking care not to pierce plastic inner flue.

5. Fix to length using self tappers provided.
6. Seal outer air duct using the tape provided.

Notes.
a.
If using the extension ducts go to Frame 18.
b. If the stand-off frame is used it is essential to add 33mm

to dimension X.

c. For shorter flue requirements less than 210mm, use non

telescopic B Pack.

1. Measure and note wall thickness X. Refer to Frame 12.
2. Add 75mm to dimension X and set telescopic flue length

as indicated in drawing.

3. Using a 3.5mm drill bit, drill two holes in outer air duct

taking care not to pierce plastic inner flue.

4. Fix to length using self tappers provided.
5. Seal outer air duct using the tape provided.

nm8944

X + 75

Drill hole

Adhere sealing tape

Measurement to be

taken from this point

nm8945

L + 115

Drill hole

Adhere sealing tape

Measurement to be

taken from this point