beautypg.com

MITSUBISHI ELECTRIC MUZ-GB50VA User Manual

Page 25

background image

25

B

B

Check of outdoor thermistors

• When OPERATION INDICATOR lamp flashes 6-time.
• When thermistor is abnormal.

Yes

Yes

No

No

Reconnect the connector CN661, CN663 and CN3.
3 minutes after turning on the power supply, start EMERGENCY OPERATION.

Defrost
Discharge temperature
Outdoor heat exchanger temperature
Ambient temperature
Fin temperature

Symbol

RT61
RT62
RT68
RT65
RT64

Connector, Pin No.

Thermistor

Board

Between CN661 pin1 and pin2
Between CN661 pin3 and pin4
Between CN661 pin7 and pin8
Between CN663 pin1 and pin2
Between CN3 pin1 and pin2

Outdoor electronic control P.C. board

Outdoor power board

Disconnect the connector in the outdoor electronic control P.C. board or the outdoor power board
(see below table), and measure the resistance of thermistor. Is the thermistor normal?

Does the unit operate 10 minutes or more without
showing thermistor abnormality?

Replace the thermistor.

Normal

Replace the outdoor electronic
control P.C. board.

OB455A--1qxq 06.7.31 2:19 PM Page 25