beautypg.com

Muz-gb50va – MITSUBISHI ELECTRIC MUZ-GB50VA User Manual

Page 23

background image

23

Part name

Figure

Check method and criterion

Defrost thermistor
(RT61)

Ambient temperature
thermistor (RT65)

Outdoor heat exchanger
temperature thermistor
(RT68)

Normal

2.6k

"

~ 3.3k

"

Normal

0.40

"

~ 0.49

"

Discharge temperature
thermistor (RT62)

Fin temperature
thermistor (RT64)

Measure the resistance between terminals using a tester.
(Winding temperature : -10°C ~ 40°C)

Compressor

W

U

V

WHT

RED

BLK

Measure the resistance between lead wires using a tester.
(Part temperature : -10°C ~ 40°C)

Outdoor fan motor

Measure the resistance using a tester. (Part temperature : -10°C ~ 40°C)

R. V. coil

Measure the resistance using a tester.(Part temperature : -10°C ~ 40°C)

Linear expansion valve

LEV

WHT

RED

YLW BRN

ORN

BLU

Color of lead wire

Normal

WHT - RED
RED - ORN

YLW - BRN

BRN - BLU

37.4

"

~ 53.9

"

MUZ-GB50VA

U

RED

WHT

BLK

V

W

(W)

(V)

(U)

Normal

RED - BLK

BLK - WHT

WHT - RED

13.4

"

~ 16.4

"

Color of lead wire

Measure the resistance with a tester.

Refer to 10-7. “Test point diagram and voltage”,1. “Outdoor electronic
control P.C. board”, the chart of thermistor.

Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.

Refer to 10-7. “Test point diagram and voltage”,1. “Outdoor electronic
control P.C. board”, the chart of thermistor.

10-5. Trouble criterion of main parts

OB455A--1qxq 06.7.31 2:19 PM Page 23