FX2N-32DP-IF Profibus-DP Interface Units
Appendix B
B-8
2) Second step in adjusting offset/gain
a) Second step in adjusting offset/gain for FX
2N
-4AD
Table B-8: Second Step in Adjusting Offset/Gain for FX
2N
-4AD
Using GSD File
User
Parameter
Type
Description
Using Programming Tool
Byte
No.
Setting
Value
(Hex)
Register
No.
Setting
Value
(Hex)
Higher/
Lower
Byte
0
00 H
User
parameter
for 32DP-IF
See section 6.1.
D200
0000 H
Lower
1
00 H
Higher
2
DA H
User
parameter
for special
function
block
(FX
2N
-4AD)
BFM #30 lower byte “DA H”
D201
07DA H
Lower
3
07 H
BFM #30 higher byte “07 H”
Higher
4
0F H
Total length of parameter bytes for this
special function block is 15 bytes (byte
No. 4 ~ 18).
D202
040F H
Lower
5
04 H
Example: number of BFM for data
exchanged every cycle is 4
BFMs (BFM #9 ~ #12).
Higher
6
09 H
Specified exchange, ex. BFM #9
D203
0A09 H
Lower
7
0A H
Specified exchange, ex. BFM #10
Higher
8
0B H
Specified exchange, ex. BFM #11
D204
0C0B H
Lower
9
0C H
Specified exchange, ex. BFM #12
Higher
10
97 H
Example: If offset data is set to “0 V”,
BFM #23 is set to “0000 H”.
D205
H0097
Lower
11
00 H
BFM #23 lower byte: “00 H”
Higher
12
00 H
BFM #23 higher byte: “00 H”
D206
9800 H
Lower
13
98 H
Example: If gain data is set to “7 V”,
BFM #24 is set to “1B58 H”
Higher
14
58 H
BFM #23 lower byte: “58 H”
D207
1B58 H
Lower
15
1B H
BFM #23 higher byte: “1B H”
Higher
16
96 H
Example: If adjusting ch 1, BFM #22 is
set to “0003 H”
D208
0396 H
Lower
17
03 H
BFM #22 lower byte: “03 H”
Higher
18
00 H
BFM #22 higher byte: “00 H”
D209
0000 H
Lower
-
-
-
Higher