beautypg.com

1 32dp-if status (m8000 ~ m8009 and d8000 ~ d8009) – MITSUBISHI ELECTRIC FX2N User Manual

Page 30

background image

FX2N-32DP-IF Profibus-DP Interface Unit

Advanced Devices 4

4-4

4.2.1

32DP-IF Status (M8000 ~ M8009 and D8000 ~ D8009)

Figure 4.2: Momentary Power failures

Figure 4.3: 32DP-IF Version

Table 4.3: Special Auxiliary Relays (M8000 ~ M8009)

Diagnostic

Device

Name

Description

M8000

(

)

RUN LED monitor

ON when 32DP-IF is exchanging data with extension I/O
blocks/units and special. This device operate same as RUN
LED.

M8001 ~ M8003

Reserved

M8004

(

)

(ref. D8004)

Error occurrence

ON when one or more error flags (M8060 to M8068) is ON. If
this bit is ON, error number is written in D8004.

M8005, M8006

Reserved

M8007

(

) (

)

(ref. D8007)

Momentary
power failure

See Figure 4.2.

M8008, M8009

Reserved

Table 4.4: Special Data Registers (D8000 ~ D8009)

Diagnostic

Device

Name

Description

D8000

Reserved

D8001

(

)

32DP-IF version

This value is 32DP-IF version code. See Figure 4.3.

D8002, D8003

Reserved

D8004

(

) (

)

Error number
M

The contents of this register

identifies which error flag

is active, i.e. if

= 8061, identifies M8061

D8005, D8006

Reserved

D8007

(

) (

)

Number of
momentary
power failures

This value is counted when M8007 is ON. This value is reset
on full power OFF.

D8008

(

)

Power failure
detection period

Power failure detection period is 10 ms.

D8009

Reserved

AC Power

Exchanged
with DP-master

M8007
Momentary power failure

10 ms

5 ms

This time is power failure detection period.

Version No.: Ex. 100 = V1.00

Module Type No.: Ex. 20 = 32DP-IF

dec