beautypg.com

MITSUBISHI ELECTRIC FX2N User Manual

Page 37

background image

FX2N-32DP-IF Profibus-DP Interface Unit

Advanced Devices 4

4-11

Table 4.12:Special Data Registers (D8060 ~ D8069)

Diagnostic

Device

Name

Error

code

Description

D8060 (

)

(

)

I/O configuration
error

This device contains the lowest device address that caused the
error. Check D8061

D8061 (

)

(

)

32DP-IF hard-
ware error

0

No error

6102

Operation circuit error: Please contact a service represen-
tative.

6103

I/O bus error: Check extension cable for Extension I/O
units/blocks.

6129

BFM #29 (error status) of a connected special function
block shows a value that is different from “0”. Please
check the diagnosis message at the DP-master.

D8062, D8063

Reserved

D8064 (

)

(

)

Parameter error

0

No error

6406

Parameter error for extension units/blocks: Check error
code in D8068, and parameter in the DP-master.

6407

Parameter length error: Parameter data too long, check
parameter’s length in the DP-master.

D8065,D8066

Reserved

D8067 (

)

(

)

Operation error

0

No error

6708

Operation error: Operation error for transmitting special
function block is occurred, check error code in D8068, and
DP-master parameter, and extension cable.

D8068 (

)

(

)

Parameter error
and operation
error

This device contains the lowest special function block’s address
that caused the error. Check D8064 and D8067.

D8069

Reserved