Appendix a: default parameter Page 53
Page 53
Appendix A
A-1
Appendix A:
Default Parameter
A-1
User Parameter
Figure A-1:User Parameter
*1 Type code of special function block is as following table. This code in the parameter must
be written first Lower byte and second higher byte
*2 After power on, the default setting of this parameter for every special function block is 2.
User Parameter for 32DP-IF
Byte No.
0
1
Bit 0
Bit 1
Bit 2
Meaning
Reserved
(must be 0)
Swap data flag
I/O block status is
checked in every
cycle: Y/N
Special function
block’s BFM #29
(Error status) is
checked: Y/N.
Description
Default setting is
OFF (0), byte data
are not swapped
within a word.
Default setting is
OFF (0), the status
check of the I/O
units/blocks is not
performed in every
cycle.
Default setting is
OFF (0), BFM #29
of all connected
special function
blocks is not
checked in every
cycle.
User Parameter for First Special Function Block
Byte No.
3
4
5
6
Meaning
Type code of special
function block, lower
byte of BFM 30
*1
Type code of special
function block,
higher byte of BFM
30
*1
Total length m of
parameter data for
this special function
block.
Contains n = 0, as
BFM addresses will
be assigned dynam-
ically
*3
Description
m = 2
*2
.....
User Parameter for Last (y
*4
th) Special Function Block
Byte No.
.....
2 + 4
×
(y
*4
- 1) + 1
....
2 + 4
×
y
*4
Meaning
.....
Type code of special
function block, lower
byte of BFM 30
*1
.....
Contains n = 0, as
BFM addresses will
be assigned dynam-
ically
*3
Description
Table A-1: Type Code of Special Function Blocks
Type
BFM 30 Code Dec
BFM30 Code Hex
FX
2N
-4AD
K2010
07DA Hex
FX
2N
-4AD-TC
K2030
07EE Hex
FX
2N
-4AD-PT
K2040
07F8 Hex
FX
2N
-4DA
K3020
0BCC Hex
FX2N-32DP-IF Profibus Interface unit