beautypg.com

3 performance specifications, Performance specifications -2 – MITSUBISHI ELECTRIC FX2N User Manual

Page 26

background image

FX2N-32DP-IF Profibus-DP Interface Unit

Specifications 3

3-2

3.3

Performance Specifications

Table 3.3: Performance Specifications

Items

Specifications

Maximum Number of Controllable
I/O Points

Maximum 256 points (see section 1.3)

Transmission data
(Maximum exchanged data length)

400bytes can be sent and received during one bus cycle.
(input: 200 bytes, output: 200 bytes)

Transmission Type

Bus network

Connector

9 pin D-SUB

Connector for Profibus-DP network

8 pin mini DIN

Connector for FX-20P-E or personal computer (MELSEC
MEDOC PLUS)

Supported Baud
Rates and Bus
Length (bps)

9.6k, 19.2k,
45.45k, 93.75k

1,200 m (3,937')

187.5k

1,000 m (3,281')

500k

400 m (1,312')

1.5M

200 m (656')

3M, 6M, 12M

100 m (328')

LED Indicators

POWER LED

ON when AC power is supplied.

RUN LED

ON when 32DP-IF is exchanging data with extension I/O blocks/
units and special function blocks.

BF LED

ON when a communication error is detected. (No data exchange)

DIA LED

ON when notice of diagnostic data is detected.