B-1-3 example setting for fx2n-4ad-pt, B-1-3 example setting for fx – MITSUBISHI ELECTRIC FX2N User Manual
Page 57
FX2N-32DP-IF Profibus-DP Interface Units
Appendix B
B-3
B-1-3
Example Setting for FX
2N
-4AD-PT
For BFM’s definition, refer to FX
2N
-4AD-PT User’s Manual.
Table B-3: User Parameter for FX
2N
-4AD-PT
Using GSD File
User
Parameter
Type
Description
Using Programming Tool
Byte No.
Setting
Value
(Hex)
Register
No.
Setting
Value
(Hex)
Higher/
Lower
Byte
0
00 H
User
parameter
for 32DP-IF
See section 6.1.
D200
0000 H
Lower
1
00 H
Higher
2
F8 H
User
parameter
for special
function
block
(FX
2N
-4AD-
PT)
BFM #30 lower byte: “F8 H”
D201
07F8 H
Lower
3
07 H
BFM #30 higher byte: “07 H”
Higher
4
06 H
Total length of parameter bytes for this
special function block is 9 bytes (byte
No. 4 ~ 9).
D202
0406 H
Lower
5
04 H
Example: number of BFM for data
exchanged every cycle is 4
BFMs (BFM #9 ~ #12).
Higher
6
09 H
Specified exchange, ex. BFM #9
D203
0A09 H
Lower
7
0A H
Specified exchange, ex. BFM #10
Higher
8
0B H
Specified exchange, ex. BFM #11
D204
0C0B H
Lower
9
0C H
Specified exchange, ex. BFM #12
Higher