CDVSC7 & CDV7 Series Gas Fireplace

18

69D3011

3"

1"

1"

1"

FP2288
TV rear vent

VenTInG InSTallaTIon

Figure 14 -
Combustible Clearances for Vent Pipe

A Minimum of 3" Clearance
to the Top Is Required
Along Horizontal Length
until Flue Pipe Penetrates
Outside Wall.

A Minimum 1"
C l e a r a n c e t o
Combustibles
P e r m i t t e d A l l
Around Flue at
Outside Wall

VenT pIpe CleaRanCeS

Rear Vent: horizontal sections of this vent
system require a minimum of 3" clearances
to combustibles at the top of the flue and
1" clearance at the sides and bottom until
the flue penetrates the outside wall.
a
minimum 1" clearance all around the flue
is acceptable at this point of penetration.
Vertical sections of this vent system require
a minimum of 1" clearance to combustibles
on all sides of the pipe.

w

a

R

n

In

G

Top Vent: horizontal sections of this vent
system require a minimum of 3" clearances
to combustibles at the top of the flue and
1" clearance at the sides and bottom until
the flue penetrates the outside wall.
a
minimum 1" clearance all around the flue
is acceptable at this point of penetration. If
vertical rise is 7

1

/

2

feet or higher when top

venting, the clearance to combustibles is
1" on all sides of the horizontal run.
Vertical sections of this vent system require
a minimum of 1" clearance to combustibles
on all sides of the pipe.

w

a

R

n

In

G

1"

3"

1"1"

FP2289
RV rear vent

A Minimum of 3" Clearance
to the Top Is Required Along
Horizontal Length until Flue
Pipe Penetrates Outside
Wall.

A Minimum 1" Clearance
to Combustibles Permitted
All Around Flue at Outside
Wall

FP88

FP89

CDVR Series

CDVT Series