how To uSe The VenT GRaph

The Vent Graph should be read in conjunction with the
following vent installation instructions to determine the re-
lationship between the vertical and horizontal dimensions
of the vent system.
1. Determine the height of the center of the horizontal

vent pipe exiting through the outer wall. Using this di-
mension on the Sidewall Vent Graph, Figure 13, locate
the point intersecting with the slanted graph line.

. From the point of this intersection, draw a vertical line

to the bottom of the graph.

3. Select the indicated dimension, and position the fire-

place in accordance with same.

exaMple a:
If the vertical dimension from the floor of the unit is 11’ (3.4
m) the horizontal run to the face of the outer wall must not
exceed 14’ (4.3 m).
exaMple B:
If the vertical dimension from the floor of the unit is 7’ (.1
m), the horizontal run to the face of the outer wall must not
exceed 8’ (.4 m).
Refer to Page 24 for snorkel requirements.

40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10

8
6
4
2

2  4  6  8 10 12 14 16 18 20

eg: A

FP2291
vent graph

X

V

ertical Dimension from the Floor of Unit to the Center of

the Horizontal V

ent Pipe

Horizontal Dimension From the Outside of Termination to

the Back of the Fireplace

Figure 13 -
Side Wall Venting Graph

X = " minimum for 33" Model
X = 5Z\v" minimum for 36", 4" and 47" Models
(Floor to center of horizontal pipe)

VenTInG InSTallaTIon InFoRMaTIon