9700 SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

v

MITSUBISHI ELECTRIC 9700SERIES UPS

WARNING 2

This UPS does not include a Bypass Input circuit breaker (MCCB). The

Bypass Input contactor (CB3) does not protect against load induced

short circuits. The bypass input circuit breaker (MCCB) is field supplied

and installed. Breaker(MCCB)'s Specifications are as follows:

Capacity (kVA) Bypass Voltage (VAC) Maximum Bypass

Rating (AAC)

Recommended

Breaker (A)

100

208

278

350

100

480

120

150

100

600

96

100

150

208

416

500

150

480

180

225

150

600

144

150

225

208

625

700

225

480

271

300

225

600

217

225

300

480

361

400

300

600

289

300

375

480

451

500

375

600

361

400