9700 SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-11

MITSUBISHI ELECTRIC 9700 SERIES UPS

NOTE:

The UPS is equipped with a selectable output contact feature. The above

alarms are the default settings. Contact MITSUBISHI ELECTRIC

AUTOMATION, INC. for set-up information

.

B) Input Contacts(for remote access of UPS)

External contacts are provided by the user of the UPS system. Terminal voltage at

the UPS is 24Vdc. Provide external dry contact accordingly.

NOTE:

Do not apply voltage to remote access input terminals. Damage to UPS

may result

.

Refer to Figure 2.17 for typical wiring configuration. Although this figure applies to the

remote start/stop terminals, the same wiring arrangement is used for emergency stop;

asynchronous command; power demand; battery temperature high.

FIGURE 2.17 Remote "Start" Contact Connections

Start

Relay Coil current : 8.3mA

Use Momentary Switches

UPS Cabinet

External to UPS
Cabinet

Relay

Coil

24 VDC

Start

Switch

Common

Details of input contacts for remote access :

Terminals 7 to 8

"Emergency Stop" contact input

Used to perform a remote UPS emergency power off (EPO).

The load will be dropped.

Terminals 9 to 10

Remote "Inverter Stop

” input terminal (IN0)

Used to stop inverter from a remote location. UPS must be programmed for

remote operation. Refer to Operations Menu for procedure.

Terminals 11 to 12 Remote "Inverter Start

” input terminal (IN1)

Used to start inverter from a remote location. UPS must be programmed for

remote operation. Refer to Operations Menu for procedure.

Terminals 13 to 14 "Power Demand Command" contact input (IN2)

Used to control the input current limit to the UPS converter (usually during