9700 SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-11
MITSUBISHI ELECTRIC 9700 SERIES UPS
TABLE 1.5 Rating of Circuit Breakers (MCCB) and Fuses
NUMBER
APPLICATION
OUTPUT CAPACITY OF EQUIPMENT
100kVA
150kVA
225kVA
300kVA
375kVA
208V
480V
600V
208V
480V
600V
208V
480V
600V
480V
600V
480V
600V
M
CB1
AC input circuit breaker
-
-
-
-
-
-
-
-
-
600A
400A
800A
600A
C
52RC
AC input contactor
350A
420A
660A
-
-
C
CB2
Battery disconnect circuit
breaker
400A
600A
800A
1200A
1600A
B
CB101
Control circuit breaker
15A
30A
F
FCU, FCV, FCW,
FCX, FCY, FCZ
Converter main circuit fuse
450A
630A
900A
900A
800A
U
FIU, FIV, FIW,
FIX, FIY, FIZ
Inverter main circuit fuse
450A
630A
900A
900A
800A
(OPTION)
FSU, FSV, FSW
Bypass main circuit fuse
450A
-
630A
-
900A
-
-
-
S
FUD1, 2
Control power fuse
DC500V 3A
DC500V 3A
DC500V 3A
DC500V 3A
DC500V 3A
E
FUS1, 2, 3
Bypass input ZNR fuse
AC600V 10A
AC600V 10A
AC600V 10A
AC600V 10A
AC600V 10A
S
FZS1, 2, 3
Bypass input ZNR fuse
AC600V 30A
AC600V 30A
AC600V 30A
AC600V 30A
AC600V 30A
FBS1, 2
CB3 control circuit fuse
AC600V 5A
AC600V 5A
AC600V 5A
AC600V 5A
AC600V 5A
FZC1, 2, 3
AC input ZNR fuse
AC600V 30A
AC600V 30A
AC600V 30A
AC600V 30A
AC600V 30A