9700 SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-3

MITSUBISHI ELECTRIC 9700 SERIES UPS

1.2 Overview

The UPS provides two power paths between the utility source and the critical load as

shown in figures 1.1 and 1.2.

A) Through the UPS Module (FIGURE 1.1)

FIGURE 1.1 Single Line Diagram - Normal Operation

When the load is on the Inverter, the internal control system determines which of the two

paths supplies power to the load. During normal operation, the path through the UPS

module is used.

Input AC power flows through the UPS where it is converted to DC by the Converter /

Charger. This DC power is utilized to charge the UPS battery and to provide power to the

Inverter. The Inverter converts the DC power to clean AC power to supply the critical load.

The conversion - inversion process eliminates any voltage transients or fluctuations

existing in the input power before it reaches the critical load.

* The Bypass Input circuit breaker (MCCB) for protection of the UPS and cables is field

supplied and field installed. (See WARNING 2 on page iv)

Static Transfer

Switch

AC Bypass

Input

Output

AC input

CB

CB3

52S

52C

Use supplied
MCCB

UPS Module

Battery cabinet

CB1

CB2

Power Flow

Not in Use

CONVERTER

INVERTER