9700 SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

6-4

MITSUBISHI ELECTRIC 9700 SERIES UPS

UA812

BYPASS VOLTAGE OUT

OF RANGE

Bypass voltage fell out of +/- 20% range

5

[1]

Note 5

231

UA813

BYPASS PHASE

ROTATION ERROR

Phase rotation is inverted when bypass voltage
is normal

5

[1]

242

UA814

BYPASS FREQUENCY

OUT OF RANGE

Bypass frequency fell out of inverter
synchronization follow-up range

5

[1]

Minor

Note 5

243

UA816

EXTENDED BYPASS

OPERATION

Bypass power supply continued for many hours

[1]

244

UA817

EMERGENCY STOP

ACTIVATED

Emergency stop applied

13

[2]

Minor

Flicker

232

UA819

REMOTE SWITCH

ON(START)

There is an error with the remote start switch.

12

[1]

229

UA820

REMOTE SWITCH

ON(STOP)

There is an error with the remote stop switch.

12

[1]

230

UA821

UPS STOPPED

(TRANSFER INHIBITED -
INVERTER AND BYPASS

ASYNCHRONOUS)

Transfer cannot be permitted because Bypass
voltage abnormal

5

[1]

249

UA822

GENERATOR OPERATION

, INHIBITED BYPASS

OPERATION

Transfer cannot be permitted because
Generator operation contact is ON

[1]

246

UA823

CB1 OFF

AC input circuit breaker CB1 turned OFF

6

[1]

224

UA824

CB2 OFF

Battery disconnect circuit breaker CB2 turned
OFF

7

[1]

225

UA826

CB101 OFF

Control power source breaker CB101 turned
OFF during inverter operation

8

[1]

226

UA827

52C NOT PERMITTED

"52C PERMISSION" switch turned to OFF

9

[1]

233

UA830

AC INPUT

UNDERVOLTAGE

AC input voltage fell out of - 10% range

3

[1]

234

UA831

EMERGENCY BYPASS

SWITCH ON

Emergency bypass switch turned to

10

[1]

245

UA832

INTERRUPTED

TRANSFER OCCURRED

WHEN TRANSFERRING

TO BYPASS SOURCE

When transfer to the bypass supply, occurs
interrupted transfer.

5

[1]

248

UA834

BATTERY DEPLETED

DC voltage dropped below discharge end
during inverter operation

10

[2]

Note 5

255

UA835

UPS STOPPED

(TRANSFER INHIBITED -

BYPASS INPUT

ABNORMAL)

Transfer cannot be permitted because Bypass
voltage is abnormal

[1]

250