9700 SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-4

MITSUBISHI ELECTRIC 9700 SERIES UPS

B) Internal Static Bypass Line (FIGURE 1.2)

The Internal Static Bypass line is a Hard wired line through CB3, contactor 52S which

supplies the critical load with unconditioned input power. The purpose of this line is to

route power to the critical load while the UPS module is de-energized during Start-up

before the system is fully operational.

FIGURE 1.2 Single Line Diagram- Bypass Operation

C) Inverter supply at battery operation (FIGURE 1.3)

FIGURE 1.3 Single Line Diagram - Battery Operation

If the input power is interrupted, the battery will immediately supply the DC power required

by the Inverter to maintain continuous AC power to the load. A fully charged battery will

provide power for the specified time at the rated load, or longer, at a reduced load.

Static Transfer

Switch

AC Bypass
Input

Output

AC input

CB

CB3

52S

52C

Use supplied
MCCB

UPS Module

Battery cabinet

CB1

CB2

Power Flow

Not in Use

CONVERTER

INVERTER

Static Transfer

Switch

AC Bypass
Input

Output

AC input

CB

CB3

52S

52C

Use supplied
MCCB

UPS Module

Battery cabinet

CB1

CB2

Power Flow

Not in Use

CONVERTER

INVERTER