9700 SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-1

MITSUBISHI ELECTRIC 9700 SERIES UPS

3.0 INSTALLATION AND OPERATION

3.1 Transportation and Installation

TABLE 3.1 How to transport and install the system

Transportation

Installation

Transport unit with forklift.
Use eye bolts (supplied) to carry with
overhead crane.

Using the holes (4 - 24) pre drilled into the
UPS channel base, anchor the unit using
appropriate hardware.

Note :

Do not transport in a horizontal position. Cabinets should be maintained

upright within +/- 15° during handling

.

3.2 Installation Procedure

A) Note the load tolerance of the floor

Refer to Table 3.2 for list of weights of UPS

’s.

TABLE 3.2 List of UPS weights

UPS Capacity (kVA)

100

150

225

300

375

Weight

(lb.)

3060 3810 4960 5890 6620

B) Minimum clearance required for ventilation

Right side

1.0" (25 mm) (not required when sidecars are used)

Left side

1.0" (25 mm) (not required when sidecars are used)

Back side

0.0" (0.0 mm)

Top side

23.6" (600 mm) (for air flow)

C) Space requirement for routine maintenance

Allow the following space at the time of installation.
Front

39.4" (1000 mm)

Sides

0.0" (0.0 mm)

Rear

0.0" (0.0 mm)