GE 90-30 PLC User Manual
Page 67
3
3-34
TCP/IP Ethernet Communications User’s Manual - August 1997
GFK-1084B
Table 3-3. Status Bits (LIS Bits and Channel Status Bits)
БББББ
БББББ
Status Bits
ББББББББББББББ
ББББББББББББББ
Brief Description
БББББ
БББББ
1-6
ББББББББББББББ
ББББББББББББББ
Reserved
БББББ
БББББ
7
ББББББББББББББ
ББББББББББББББ
Serial Port #2 Fuse Blown
БББББ
БББББ
8
ББББББББББББББ
ББББББББББББББ
AAUI Fuse Blown
БББББ
9
ББББББББББББББ
Any Channel Error (error on any channel)
БББББ
БББББ
10
ББББББББББББББ
ББББББББББББББ
Reserved
БББББ
БББББ
11
ББББББББББББББ
ББББББББББББББ
Reserved
БББББ
БББББ
12
ББББББББББББББ
ББББББББББББББ
Reserved
БББББ
БББББ
13
ББББББББББББББ
ББББББББББББББ
LAN OK
БББББ
БББББ
14
ББББББББББББББ
ББББББББББББББ
Resource Problem
БББББ
15
ББББББББББББББ
Reserved
БББББ
БББББ
16
ББББББББББББББ
ББББББББББББББ
LAN Interface OK
БББББ
БББББ
17
ББББББББББББББ
ББББББББББББББ
Data Transfer - Channel 1
БББББ
БББББ
18
ББББББББББББББ
ББББББББББББББ
Channel Error - Channel 1
БББББ
БББББ
...
ББББББББББББББ
ББББББББББББББ
...
БББББ
БББББ
47
ББББББББББББББ
ББББББББББББББ
Data Transfer - Channel 16
БББББ
48
ББББББББББББББ
Channel Error - Channel 16
БББББ
БББББ
49-80
ББББББББББББББ
ББББББББББББББ
Reserved for future use
Note
Unless the “LAN Interface OK” bit is set (Status Bit 16), the other status
bits are invalid.
(Status Bit 7) Serial Port #2 Fuse Blown:
This bit is set to 1 when the Serial Port #2 fuse
is blown. Otherwise it is set to 0.
(Status Bit 8) AAUI Fuse Blown:
This bit is set to 1 when the AAUI Fuse is blown. Other-
wise it is set to 0.
(Status Bit 9) Any Channel Error:
This bit is set to 1 if there is presently an error on any
of the established channels; i.e., if the individual Channel Error bit is set for any channel.
(Status Bit 13) LAN OK:
T
his input will be held at the value 1 as long as the Ethernet
Interface software is able to communicate on the network. If the network should be-
come inaccessible from this Interface, due either to local or network problems, this bit
will be set to 0. If LAN communication becomes possible, it is set to 1.
(Status Bit 14) Resource Problem:
This input is set to 1 whenever the Ethernet Interface
software experiences a resource problem (i.e., lack of data memory). The bit is reset to 0
on a subsequent PLC sweep. The Ethernet Interface may or may not be able to continue
functioning, depending on the severity of the problem. Use the PLC Fault Table to un-
derstand the problem. See Chapter 6, Troubleshooting, for further information. In
addition, you can use the Station Manager STAT B and LOG commands to further under-
stand the problem. See Chapter 5, The Station Manager, for more information.
(Status Bit 16) LAN Interface OK Bit:
This input is set to 1 by the Ethernet Interface each
PLC scan. If the Ethernet Interface cannot access the PLC, the CPU will set this bit to 0.
When this bit is 0, all other Ethernet Interface Status bits are invalid.