GE GFK-1541B User Manual
Page 106
GFK-1541B
Chapter 3 Programming Channel Commands
3-39
3
Minor Error Codes for Major Error Codes 5H and 85H (Continued)
Error Status
Service Request Error Description
(Hexadecimal)
F705H/F785H
Required to log in to a task for service.
F805H/F885H
Invalid task name referenced.
F905H/F985H
Task address out of range.
FC05H/FC85H
I/O configuration is invalid.
FE05H/FE85H
No privilege for attempted operation.
FF05H/FF85H
Service request has been aborted.
Minor Error Codes for Major Error Code 11H (at Remote Server PLC)
Error Status
(Hexadecimal)
SRTP Error Description
Error codes common to all GE Fanuc PLCs
0111H
Generic SRTP error.
0211H
The PLC is inaccessible.
0311H
Reserved.
0411H
Unexpected SRTP version encountered in received message.
0511H
Unrecognized SRTP message received.
0611H
Data present in SRTP message which should not contain data.
0711H
Generic resource problem detected.
0811H
SRTP message encountered in inappropriate connection state.
0911H
Generic refusal by backplane driver to handle request.
0A11H
Recognized but unsupported SRTP message received.
0B11H
Lost transaction in server.
0C11H
Error sending SRTP PDU to the client PLC.
Can someone explain the disclaimer below? This manual describe those four
products.
Error codes specific to IC697CMM742, IC693CMM321, IC693CPU364, and
IC693CPU374
1411H
Unable to allocate a text buffer from dual port memory.
1711H
Invalid text length detected in a mailbox message.
1811H
Invalid number of destinations detected in a mailbox message.
1911H
Invalid source detected in a mailbox message.
1A11H
Invalid slot number detected in a mailbox message.
1B11H
Invalid rack number detected in a mailbox message.
1D11H
Bad text buffer address in dual port memory.
2111H
Unable to find control data required to send a mailbox message to the PLC.
2211H
Timed out waiting for availability of mail communications with the PLC.
2311H
Invalid task ID detected while attempting to send a mailbox message to the PLC.
2411H
Unable to send mailbox message to PLC because the mail queue is full.
2611H
Unable to communicate with PLC.
2711H
Backplane driver not initialized or unable to acquire a dual port memory
semaphore.
2A11H
The backplane driver could not access the PLC.
2B11H
Invalid binding on the message sent to the backplane driver.
2C11H
The message could not be sent to its destination because the mailbox was not open.
2D11H
The maximum number of transfers to the destination is already taking place.