beautypg.com

Pilz PSSu E S 2AI RTD User Manual

Page 35

background image

Technical Details

Operating Manual PSSu E S 2AI RTD(­T)
22017­EN­06

35

Analogue inputs

312490

314490

Measuring ranges

Type

Pt100

Pt100

Measuring range

­200 ­ 850 °C

­200 ­ 850 °C

Type

Pt200

Pt200

Measuring range

­200 ­ 850 °C

­200 ­ 850 °C

Type

Pt500

Pt500

Measuring range

­200 ­ 850 °C

­200 ­ 850 °C

Type

Pt1000

Pt1000

Measuring range

­200 ­ 850 °C

­200 ­ 850 °C

Type

Ni100

Ni100

Measuring range

­60 ­ 250 °C

­60 ­ 250 °C

Type

Ni120

Ni120

Measuring range

­60 ­ 250 °C

­60 ­ 250 °C

Type

Ni1000

Ni1000

Measuring range

­60 ­ 250 °C

­60 ­ 250 °C

Type

Widerstand

Widerstand

Measuring range

0 ­ 4000 Ohm

0 ­ 4000 Ohm

Input filter

Digital filter

Digital filter

Filter time per input (2­wire meas­
urement) with attenuation

Attenuation

90 dB (60 Hz)

90 dB (60 Hz)

Filter time

103 ms

103 ms

Attenuation

80 dB (50 Hz)

80 dB (50 Hz)

Filter time

122 ms

122 ms

Attenuation

65 dB (50 Hz, 60 Hz)

65 dB (50 Hz, 60 Hz)

Filter time

122 ms

122 ms

Attenuation

69 dB (50 Hz, 60 Hz)

69 dB (50 Hz, 60 Hz)

Filter time

202 ms

202 ms

Attenuation

74 dB (50 Hz, 60 Hz)

74 dB (50 Hz, 60 Hz)

Filter time

482 ms

482 ms

Voltage measurement

Input resistance

100 MOhm

100 MOhm

Max. continuous voltage

5 V

5 V

Temperature measurement

Value of least significant bit
(LSB)

0,0625 K

0,0625 K

Resistance measurement

Value of least significant bit
(LSB)

0,0625 Ohm

0,0625 Ohm

Typ. conversion time per input

404 ms

404 ms

Max. measuring current

500 µA

500 µA

Deviations from the measuring
range limit value

Output variable error at 25 °C

0,3 %

0,3 %

Temperature coefficient

0,0040 %/K

0,0040 %/K

This manual is related to the following products: