Wiring
Operating Manual PSSu E S 2AI RTD(T)
22017EN06
28
}
On base modules with screw terminals:
–
If you use a multistrand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm
2
, Form A or C,
although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 609471, such as the PZ 1.5 or PZ 6.5 from
Weidmüller, for example.
–
Maximum torque setting: 0.8 Nm
}
Use copper wiring.
6.2
Terminal configuration
Base module
Terminal configuration
Screw terminals:
PSSu BP 1/12S
PSSu BP 1/12ST
Cage clamp terminals:
PSSu BP 1/12C
PSSu BP 1/12CT
Without Crail:
11: Input R0+
21: Input RL0+
12: Input R0
22: Input RL0
1323: Cable shield
(13231626 linked within
the base module)
14: Input R1+
24: Input RL1+
15: Input R1
25: Input RL1
1626: Cable shield
(13231626 linked within
the base module)
21
11
22
12
23
13
24
14
26
16
25
15