Wiring
Operating Manual PSSu E S 2AI RTD(T)
22017EN06
27
–
Check that the cable is firmly seated.
}
Base module with cage clamp terminals:
–
Insert the screwdriver [4] into the square hole [1].
–
Insert the stripped cable into the round fixing hole [2], as far as it will go [5].
–
Pull out the screwdriver [6].
–
Check that the cable is firmly seated.
21
11
[1]
[3]
[2]
[4]
[5]
[6]
Please note:
}
The minimum cable cross section for field connection terminals on the base modules is
0.14 mm
2
(AWG26).
}
The maximum cable cross section for field connection terminals is:
–
Digital inputs: 1.5 mm
2
(AWG16)
–
Digital outputs: 2.0 mm
2
(AWG14)
–
Inputs/outputs on the counter modules: 1.5 mm
2
(AWG16)
–
Analogue inputs/outputs: 1.5 mm
2
(AWG16)
–
Communication cables: 1.5 mm
2
(AWG16)
–
Test pulse outputs: 1.5 mm
2
(AWG16)
–
Power supply: 2.5 mm
2
(AWG12)
–
Functional earth: 2.5 mm
2
(AWG12)