8 summary and overview, Summary and overview – Pilz PSSu E S 2AI RTD User Manual
Page 19
Function description
Operating Manual PSSu E S 2AI RTD(T)
22017EN06
19
4.2.8
Summary and overview
The module has the following configuration options:
Configurable paramet
ers
Configurable values
Default
Key
Measuring range
Pt100, Pt200, Pt500, Pt1000, Ni100,
Ni120, Ni1000, 0 … 4000 Ohm
Pt100
Connection type
2wire measurement,
3wire measurement,
Connection for 4wire sensor
3wire measure
ment
2wire measurement
offset
0 … 32767
D
0
Resolution in
1/16 Ohm
Manufacturer scaling
Activated/TRUE
Manufacturer scaling
offset
32768 … 32767
D
0
Manufacturer scaling
gain
32768 … 32767
D
160
D
Amplification
factor 10/16
User scaling
Deactivated/
FALSE
User scaling offset
32768 … 32767
D
0
User scaling gain
32768 … 32767
D
256
D
Amplification
factor 1
Filter characteristic
2wire measurement:
103 ms/90 dB (60
Hz),
122 ms/80 dB (50
Hz),
122 ms/65 dB (50 Hz
and 60 Hz),
202 ms/69 dB (50 Hz
and 60 Hz),
482 ms/74 dB (50 Hz
and 60 Hz)
3wire measure
ment or 4wire
sensor connection:
206 ms/90 dB (60
Hz),
244 ms/80 dB (50
Hz),
244 ms/65 dB (50
Hz and 60 Hz),
404 ms/69 dB (50
Hz and 60 Hz),
964 ms/74 dB (50
Hz and 60 Hz)
404 ms/69 dB
(50 Hz and 60
Hz)
With 2wire
measurement,
202 ms/69 dB
(50 Hz and 60
Hz) is the default
setting
Range monitoring
Activated/TRUE
Sign and magnitude
representation
Deactivated/
FALSE
Two's comple
ment is activated
ADC raw value
No raw value,
Raw value of sensor,
Raw value of wire
No raw value