Industrial Data Systems IDS Scale Basic User Manual
Page 17

Scale Basic 4.2E
Tutorial
The Setpoint Monitor is used to generate the next event. When the setpoint event occurs, it
activates user function 2 which turns off the fill valve.
Event
Function
Comments
F1 key
User 1
Start Fill operation
Setpoint 1
User 2,
trigger when Net >= Fixed43 (setpoint amount)
Configure the Setpoint 1 event with the Upper register = Fixed43 and the Lower register = Net
weight register. This will cause the setpoint to trigger when the Net weight >= (greater than or
equal to) the value in Fixed 43. Configure the Setpoint 1 function to execute = User 2.
Register Fixed43 is chosen because the fill amount is fixed. Data in the Fixed registers is written
to EA-ROM which remains unchanged by power loss.
Function
Instructions
Comments
User 1
Copy, Tare, Gross
Tare the scale
Relay on, 1
Turn on fill valve
Set pt on, 1
Turn on setpoint monitor 1
End
End
of
function
User 2
Relay off, 1
Turn off fill valve
End
End
of
function
Parameter
Used
for
Fixed
43 setpoint
amount.
Use the template above to enter the program.
1.
Invoke the EZ Link program.
2.
Click on Reset to Defaults to clear previous program.
3.
Set Keyboard Events / F1 key = User1
4.
In Setpoint Events / Setpoint 1 set Upper = Fixed43, Lower = Net, Function = User2
5.
In Fixed Registers / Fixed43 enter 500.
6.
Scale Basic / User 1 enter the following program:
Function
Instructions
Comments
User 1
Copy, Tare, Gross
Tare the scale
Relay on, 1
Turn on fill valve
Set pt on, 1
Turn on setpoint monitor 1
End
End
of
function
5. Scale Basic / User 2 enter the following program:
Function
Instructions
Comments
User 2
Relay off, 1
Turn off fill valve
End
End
of
function