B. Supplementary information

B-26

Festo P.BE-MTR-DCI-IO-EN en 1209d

Status_Word

CI access

6041h

00h

Var

uint16

r

Description

Download current controller or regulator status.
Typical values see Tab. B/2.
Default: 0x0031

Bits 0...3, 5 and 6 show the status of the device.

Value (binary)

Status (x = irrelevant for this status)

xxxx xxxx x0xx 0000

Not ready to switch on

xxxx xxxx x1xx 0000

Switch on disabled

xxxx xxxx x01x 0001

Ready to switch on

xxxx xxxx x01x 0011

Switched on

xxxx xxxx x01x 0111

Operation enabled

xxxx xxxx x00x 0111

Quick stop active

xxxx xxxx x0xx 1111

Fault

Bit

Value

Comment

Mask open ...

0x0000

Not ready to switch on (pre-initialization status)

0x0021

Ready to switch on (status after initialization)

0x0027

Switched on + operation enable (power electronics and
positioning are enabled)

3

0x000F

Fault (there is a fault)

Bit 3: 0x0008

4

0x0010

<1>: Voltage disabled (end stage off)
<0>: Voltage enabled (end stage on)

Bit 4: 0x0010

10

0x0400

Nominal position reached
<1>: Target reached /Motion Complete (see also Object 6068)
<0>: Motion not complete

Bit 10: 0x0400

11

0x0800

I

2

t-fault

<1>: Internal limit active
<0>: Internal limit not active

Bit 11: 0x0800

13

0x2000

Fault during homing run
<1>: Homing error
<0>: No homing error

Bit 13: 0x2000

Tab. B/2:

Typical values of status word