Caution – HT instruments HT7051 User Manual
Page 25

HT2055
EN - 24
CAUTION
 When starting test the unit performs a preliminary check of the resistance
values of current probe (Rc) and voltage probe (Rp) stopping the test if 
these values are assumed to be too high and giving the messages “Rc: 
>2.0k
” and “Rp: >2.0k”. Decrease the resistance value wetting the
ground close to the probes and/or connect more probes in parallel
 High noise currents and voltages in earth could affect the measurement
results. In this case the tester displays the ”NOISE” warning
 
6 Press 
MEM
key to save the result inside memory (see § 8.1)
CAUTION
To view stored ground resistivity results on PC they must be downloaded to 
the meter unit first. To download the results select earth results in Synchronize 
menu (see § 5.1.3). After the results are downloaded the stored data in 
the station unit will be automatically deleted 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
