Specifications, Ups physical specifications, Erm physical specifications – HP R2200 User Manual
Page 45: Ups input specifications
Specifications 45
Specifications
In this section
UPS physical specifications...................................................................................................................... 45
ERM physical specifications..................................................................................................................... 45
UPS input specifications .......................................................................................................................... 45
UPS output specifications......................................................................................................................... 46
Battery specifications .............................................................................................................................. 47
Battery runtime....................................................................................................................................... 47
Environmental specifications .................................................................................................................... 47
UPS physical specifications
Parameter Value
Height
8.9 cm (3.5 in)
Depth
48.3 cm (19 in)
Width
44.5 cm (17.5 in)
Weight
29 kg (64 lb)
ERM physical specifications
Parameter Value
Height
8.9 cm (3.5 in)
Depth
34.3 cm (13.5 in)
Width
44.5 cm (17.5 in)
Weight
28.6 kg (63 lb)
UPS input specifications
NOTE: An asterisk (*) indicates the default setting.
UPS model
Utility voltage
frequency (Hz)
Available settings utility
voltage (VAC)
Branch circuit
rating (A)
Line cord
R/T2200
NA/JPN/TWN
50/60 100,
110,
120*
20
Nondetachable power
cord with NEMA 5-20
plug
R/T2200 INTL
50/60
220, 230*, 240
15
Detachable power cord
with IEC-320-C20 plug